The existing service was sized for a small shop. The mall's switchboard has the room for more.
The smaller unit runs on a 45 kVA transformer and a 100 A panel, which suited its last use but sits well short of the brand's 400 A standard. The larger unit had no service of its own yet. So we followed the feed back to the mall's main switchboard, where a 2,500 A-frame main breaker set at 2,000 A was carrying 165 A on a weekday afternoon. The capacity is there. The question is only the feeder.
What we recommended
Ask the landlord for a 200 A feeder at 480 V and a 150 kVA step-down transformer in a new tenant electrical room. That delivers the brand's 400 A at 208 V and retires the old equipment.